Proportionate Measurement
Analog-to-digital converters often produce an output that depends directly on the value of the reference voltage supplied to the circuit. Sensor systems use ratiometric calibration to remove errors caused by fluctuations in the power supply. The technique ensures that the digital reading remains a fixed fraction of the input signal regardless of the supply voltage.
This approach eliminates the need for a precision voltage reference.
Bridge Topology
Strain gauges and pressure sensors typically utilize a Wheatstone bridge configuration. In this setup, ratiometric calibration happens naturally because the excitation voltage for the bridge also acts as the reference for the converter. If the excitation voltage drops by one percent, the bridge output and the converter scale drop by the same amount.
The final digital value stays constant.
Transfer Function
Mathematically, the output code is the ratio of the input voltage to the reference voltage multiplied by the full scale of the converter. Because both voltages track the same supply, the supply term cancels out of the equation.
Accuracy Limit
Non-ideal behaviour in the converter or the sensor can still introduce errors. Input offset voltages and gain mismatches do not cancel out through ratiometric calibration alone. Engineers must perform a zero-point adjustment and a span calibration at the factory.
Ongoing monitoring ensures that the ratiometric relationship holds over the entire operating range of the device. This verification step identifies any non-linearities that the simple ratio cannot correct.