Parasitic Current
Measurement noise often originates from a circuit containing two or more points connected to ground through different impedances across a shared cabling system. A ground loop creates a closed conductive circuit that permits the flow of stray currents, often inducing noise into measurement signals through electromagnetic induction. The phenomenon typically manifests as a low frequency hum in audio systems or as unstable offsets in precision DC instrumentation where millivolt accuracy is required.
It is limited to systems where multiple grounding points exist within a single interconnected network and does not apply to fully isolated battery powered devices.
Induction Mechanism
Magnetic fields from nearby power transformers or motors pass through the loop area and generate an electromotive force. This induced voltage adds directly to the signal being measured, corrupting the data before it reaches the digitizer. Reducing the physical area of the loop by twisting signal and return wires together helps to minimize the pickup.
Mitigation Strategy
Breaking the loop requires the use of isolation techniques such as optical couplers or isolation transformers. If a ground loop persists, an engineer might employ a differential amplifier to reject the common mode noise while amplifying the desired signal. Differential sensing ignores the voltage present on both lines, focusing only on the potential difference between them.
Field Verification
Identification of the source involves measuring the potential difference between grounding terminals with a high precision voltmeter. A zero reading indicates that the points are at the same potential, whereas any measurable voltage suggests a current path exists. Removing redundant ground connections often resolves the issue, provided safety standards for chassis grounding are still met.