Geometric Boundary
Multi-axis sensor outputs often lie on a three-dimensional curved envelope due to scaling and bias distortions. This quadric surface describes the geometric shape of the sensor outputs before any correction is applied. It identifies the mathematical nature of the systematic errors in the measurement system.
Sensor Distortion
Accelerometers and magnetometers can exhibit non-linearities that warp their measurement locus from a sphere to an ellipsoid, paraboloid, or hyperboloid. Fitting a quadric surface to these data points provides the coefficients needed to calculate the calibration matrix. Once the coefficients of the surface are known, the correction algorithm can reconstruct the undistorted sensor signals by mapping the warped envelope back to a sphere.
Mathematical Modeling
Equations defining these structures use quadratic terms to represent the interaction between the sensor axes. The quadric surface model captures the combined effects of cross-axis sensitivity, gain mismatches, and sensor offsets. This unified model simplifies the calibration task by addressing multiple error sources within a single algebraic expression.
Calibration Geometry
Metrology systems use these models to check the accuracy of the multi-axis sensor arrays. When the quadric surface coefficients are calculated, they are compared against the factory defaults to detect mechanical shifts. This verification ensures that the sensor module operates within its specified structural and measurement limits.